Inspection
Inspection Details
Equipment ID
927
927
Inspection Date
2/22/2019
2/22/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Harris
David Harris
Mechanic Name
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
b43ba9e8-bff7-4092-8432-49c98b9b52cd
b43ba9e8-bff7-4092-8432-49c98b9b52cd
Location
Kelly Plaza
1900 S PROVIDENCE RD, COLUMBIA, MO
1900 S PROVIDENCE RD, COLUMBIA, MO
Owner
Atkins Investments
PO BOX 756, COLUMBIA, MO 65205-0756
PO BOX 756, COLUMBIA, MO 65205-0756
Billing
Attn: Atkins Investments
PO BOX 756, COLUMBIA, MO 65205-0756
PO BOX 756, COLUMBIA, MO 65205-0756
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is expired, have serviced or replaced | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is not working. Re-inspection required | 1/7/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Need to install self locking machine room door | 1/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Need to install pit ladder | 1/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Need to install sump hole cover | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell is not working. Re-inspection required | 1/7/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Need to install self locking door | 1/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to install pit ladder | 1/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to install sump pump hole cover | 1/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | NEEDS SUMP HOLE COVER | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | NEEDS TO PROVIDE A SELF-LOCKING DOOR HANDLE | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | MUST HAVE A CURRENT TEST TAG |