Inspection
Inspection Details
Equipment ID
3768
3768
Inspection Date
7/21/2026
7/21/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
18
18
External ID
5b951dfe-52a5-42ed-ad18-ee129f39b807
5b951dfe-52a5-42ed-ad18-ee129f39b807
Location
Iatan Powerhouse
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3613
Email: donald.hughes@evergy.com
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3613
Email: donald.hughes@evergy.com
Owner
Attn: Steven Thomas
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: steven.d.thomas@evergy.com
Billing
Attn: Kevin Cook
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: kevin.cook@evergy.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | 8.11.2.3.1 | Yes | Yes | Need to perform full load safety test. Elevator would not lift rated load | 7/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | No | Elevator would not lower, stop, and hold 125% of rated load. | 7/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not call out | 5/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure in machine room | 7/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 7/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Control space access door needs to be self-locking and non-defeatable | 7/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | All elevators in the same building shall use the same key for firefighter operation. | 5/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide lighting of control space. Light fixture does not illuminate | 7/21/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan in the machine room | 7/21/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan in the machine room | 7/21/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records in the machine room | 7/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | All elevators in the same building shall have firefighter keyswitches operated by the same key | 5/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not illuminate | 5/22/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 5/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate displayed | 7/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone speaker volume is to low. Cant hear person on the line. | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | No | No | Car lighting is less than 5 foot candles with the doors closed. Need to increase the illumination inside the elevator | 7/21/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. | 7/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone |