Inspection
Inspection Details
Equipment ID
9658
9658
Inspection Date
7/29/2026
7/29/2026
Inspection Type
Reinspection
Reinspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
0b1d02b3-3b30-4103-a03c-09c3833946b7
0b1d02b3-3b30-4103-a03c-09c3833946b7
Location
SSM-De Paul Health Center
12255 De Paul Dr, Bridgeton, MO
Phone: (314) 344-6104
Email: Teresa.horn@ssmhealth.com
12255 De Paul Dr, Bridgeton, MO
Phone: (314) 344-6104
Email: Teresa.horn@ssmhealth.com
Owner
Attn: Teresa Horn | Facilities Compliance Specialist
SSM-De Paul Health Center
12303 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 344-6104
Email: Teresa.horn@ssmhealth.com
SSM-De Paul Health Center
12303 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 344-6104
Email: Teresa.horn@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 2/7/0202 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | There are a number of Braille floor indicating tags missing on multiple floors and shall be reinstalled for proper floor identification. | 7/30/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. An alteration permit and reinspection are required. | 12/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance. | 6/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Yes | No | Suspension rope tensions should be substantially equalized. Load-weigher device is not working (shows ERR). Repair/replace as needed. | 12/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Yes | No | 2.20.9.5.4 - Suspension rope retaining clips at improper distances. Adjust for proper clearance. | 12/8/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The unintended motion testing shall be performed before the inspection is completed. | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | 6/19/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. | 6/11/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required | 6/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance. | 7/29/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required | 7/29/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | When testing the elevator on emergency power, the emergency power jewel at the main lobby failed to illuminate. Needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance. |