Inspection
Inspection Details
Equipment ID
25581
25581
Inspection Date
8/4/2026
8/4/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Travis Cardona
Travis Cardona
Relief Valve Pressure
NA
NA
Slide
Softset
Softset
Governor Rope Pull
Softset
Softset
Door Closing Force
14/15
14/15
External ID
638e9bdd-098d-4699-8962-283bf37b71a1
638e9bdd-098d-4699-8962-283bf37b71a1
Location
MLS
326 S 21st St, St. Louis, MO
Phone: (314) 511-2294
Email: pcaldwell@stlcitysc.com
326 S 21st St, St. Louis, MO
Phone: (314) 511-2294
Email: pcaldwell@stlcitysc.com
Owner
Attn: Pharron Caldwell
TKFC LC
1 Center Circle, St. Louis, MO 63103
Phone: (314) 339-0401
Email: pcaldwell@stlcitysc.com
TKFC LC
1 Center Circle, St. Louis, MO 63103
Phone: (314) 339-0401
Email: pcaldwell@stlcitysc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Emergency communications loss monitor shall work. | 2/22/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Voice does not work but video/text works. | 2/22/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/12/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.7.2 Seizing of Rope Ends | No | No | 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. | 9/12/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | No | No | 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cartop light does not work. | 9/12/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Take corrective action and re-test. | 12/8/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby does not meet Code Minimum of 6". | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.11.2.1.2(g) | No | No | Non-elevator related items shall not be stored in Machine Room | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet |