Inspection
Inspection Details
Equipment ID
1160
1160
Inspection Date
1/28/2019
1/28/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Joseph Ammons
Joseph Ammons
Relief Valve Pressure
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
24
24
External ID
881ea0fb-caa0-423a-9e07-6a0d0a1149db
881ea0fb-caa0-423a-9e07-6a0d0a1149db
Location
Truman Building
301 W HIGH ST, JEFFERSON CITY, MO
301 W HIGH ST, JEFFERSON CITY, MO
Owner
Attn: INTERAGENCY
State of Missouri- Truman Bldg-INTERAGENCY
301 W HIGH ST STE 730, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
State of Missouri- Truman Bldg-INTERAGENCY
301 W HIGH ST STE 730, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
Billing
Attn: INTERAGENCY
OA- FMDC-HST RM 730-INTERAGENCY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
OA- FMDC-HST RM 730-INTERAGENCY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Clean car top. | 1/31/2026 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit. | 1/31/2026 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Clean machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Shorten ropes, no runby present. | 2/22/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Provide door maintenance on all floors. Rollers, upthrust devices, gibs, etc. All items showing wear and in need of maintenance. | 2/22/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Provide monthly FFS testing log in machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide MCP in machine room. | 1/31/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Emergency power not tested at time of inspection. | 2/22/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide MCP in machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Shorten main hoisting ropes, only 1" of runby in pit. | 1/10/2024 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 1/31/2026 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | Emergency power not tested at time of inspection. | 1/10/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Shorten ropes, no runby in pit. | 1/23/2025 |