Inspection
Inspection Details
Equipment ID
10166
10166
Inspection Date
7/31/2026
7/31/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Leland Jones
Leland Jones
Mechanic Name
Jason Hernke
Jason Hernke
Relief Valve Pressure
540
540
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
8f3dca63-9d52-45ba-b9c3-f922a60ee748
8f3dca63-9d52-45ba-b9c3-f922a60ee748
Location
Smithton Middle School
3600 W Worley St, Columbia, MO
Phone: (573) 886-2243
3600 W Worley St, Columbia, MO
Phone: (573) 886-2243
Owner
Attn: Columbia Public Schools
Columbia Public Schools
5909 Paris Rd, Columbia, MO 65202
Phone: (573) 289-1314
Email: Jgipson@cpsk12.org
Columbia Public Schools
5909 Paris Rd, Columbia, MO 65202
Phone: (573) 289-1314
Email: Jgipson@cpsk12.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | When shutting off C/B for car lights to check emergency battery shunt trip breaker shuts down elevator when you turn the C/B for car lights back on. Whoever wired in shunt tip did not do it correctly in must be corrected. | 9/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | NEC 620 When shutting off C/B for car lights to check emergency battery, shunt trip breaker shuts down elevator when you turn the C/B for car lights back on. Whoever wired up Shunt trip did not do it correctly. It must be corrected. 2nd Request. | 9/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need In Case of Fire signs by each hall call button | 12/21/1202 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Phone is not working. Line to controller is good. | 8/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 6/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire use stairs signage needed | 12/21/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 12/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Phone? | 7/17/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 12/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Line? | 4/2/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 12/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Phone line good. Needs programming from bldg IT department | 7/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | STANDBY POWER MUST BE MADE OPERABLE | 7/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE MUST BE MADE OPERABLE | 7/31/2026 |