Inspection
Inspection Details
Equipment ID
17085
17085
Inspection Date
2/12/2019
2/12/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
640
640
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
b2789bd6-c11b-4d13-8c88-988d79d039c9
b2789bd6-c11b-4d13-8c88-988d79d039c9
Location
Villas at Brentwood
1800 S BRENTWOOD BLVD, SAINT LOUIS, MO
1800 S BRENTWOOD BLVD, SAINT LOUIS, MO
Owner
Villas at Brentwood
1800 S BRENTWOOD BLVD, SAINT LOUIS, MO 63144-1820
1800 S BRENTWOOD BLVD, SAINT LOUIS, MO 63144-1820
Billing
Attn: Villas at Brentwood
1800 S BRENTWOOD BLVD, SAINT LOUIS, MO 63144-1820
1800 S BRENTWOOD BLVD, SAINT LOUIS, MO 63144-1820
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Car top inspection station not working | 2/6/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 8/11/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean up soaked pads on pit floor. | 8/11/2025 |
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 1001.2(c)(3) | No | No | Car top pendant station inoperative. Repair | 8/11/2025 |
| A17.1-1996 : Elevators | 1.13 - Emergency exit | 1001.2(a)(13) | No | No | Car top emergency escape hatch unsecured. Secure hatch. | 8/11/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Recall from hall key switch inoperative. Repair. | 1/8/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Fire service key switch at first floor egress will not turn. Smokes are operating. Did not red tag unit. Reinspect Phase I & II | 10/23/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 2/11/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | OSV in the pit is due for testing, provide. | 1/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Repair 1st floor door closer. Door not closing on it's own | 2/11/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Escape hatch secured with bolts Hatch needs thumb screws or wing bolts | 2/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone | 3/12/2025 |