Inspection
Inspection Details
Equipment ID
23764
23764
Inspection Date
8/17/2026
8/17/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Steven Crim
Steven Crim
Relief Valve Pressure
540
540
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
32
32
External ID
eff5e76a-b333-4af5-bb36-46e8165dd482
eff5e76a-b333-4af5-bb36-46e8165dd482
Location
Mark Twin Behavioral Health
154 Forrest Dr, Hannibal, MO
Phone: (000) 000-0000
154 Forrest Dr, Hannibal, MO
Phone: (000) 000-0000
Owner
Attn: Mark Twain Behavioral Health
Mark Twain Behavioral Health
154 FORREST DR, HANNIBAL, MO 63401
Phone: (573) 221-2120
Email: mtbhbilling@mtbh.org
Mark Twain Behavioral Health
154 FORREST DR, HANNIBAL, MO 63401
Phone: (573) 221-2120
Email: mtbhbilling@mtbh.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.3.2 | Yes | No | No Pit Light. | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | Yes | No | Drain Lines in Machine Room. | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | Yes | No | Seal penetrations. | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | No flashing fire hat. | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | Yes | No | Provide "Do not use in case of fire" signage all floors. | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Provide fire extinguisher. | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.1 - Top-of-car stop switch | 2.26.2.8 | Yes | No | top of car "stop switch" not working | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide working phone. | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | Yes | No | Provide facia 1st & 2nd floors | 8/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Provide working car door restrictor. | 8/27/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Phone? | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Car door pressure over 30 lbs |