Inspection
Inspection Details
Equipment ID
13215
13215
Inspection Date
8/27/2026
8/27/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Keith Galvin
Keith Galvin
Mechanic Name
Justin DeBrot
Justin DeBrot
Relief Valve Pressure
470
470
Slide
00
00
Governor Rope Pull
00
00
Door Closing Force
27
27
External ID
13673ed1-090c-47ca-b480-b92e7ab39a1b
13673ed1-090c-47ca-b480-b92e7ab39a1b
Location
Forest View
1624 W White Oak St, Independence, MO
Phone: (816) 254-3500
1624 W White Oak St, Independence, MO
Phone: (816) 254-3500
Owner
Attn: J. Head
The Groves
1515 W White Oak St, Independence, MO 64050
Phone: (816) 254-3500
Email: jhead@thegroves.com
The Groves
1515 W White Oak St, Independence, MO 64050
Phone: (816) 254-3500
Email: jhead@thegroves.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Non elev.related wiring in hoistway | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Door to mach. room needs to be self closing an self locking | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Non elev. related material in mach. room | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Fire serv. signage in car not correct | 9/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Wiring in hoistway not enclosed | 9/5/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | materials not nesseary for the maint. or operation of elev. stored in mach. room | 1/10/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach. room door needs to be self locking | 1/10/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | materials in mach. room that are not related to elev. operation | 12/17/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | need self locking doorknob | 12/17/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | need sump pump cover | 12/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emg phone not working | 12/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 8/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | didnt have correct fitting to test relief valve | 3/12/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door lock doesnt lock when door closes | 8/27/2026 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | need phase one an two fire serv signage | 8/27/2026 |
| A17.1-2016 : Elevators | 3.3 - Top-of-car operating device | 2.26.1.4 | No | No | car top insp dn button didnt work | 8/27/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | out of date |