Inspection
Inspection Details
Equipment ID
16015
16015
Inspection Date
8/31/2026
8/31/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
21 lbs
21 lbs
External ID
5bb550b4-0904-490a-b993-4666e99d9b17
5bb550b4-0904-490a-b993-4666e99d9b17
Location
Winter Garden Apartments
5708 Kingsbury Pl, St. Louis, MO
Phone: (314) 361-7225
5708 Kingsbury Pl, St. Louis, MO
Phone: (314) 361-7225
Owner
Attn: Winter Garden Preservation, LP
RMC-Related Management Company
60 Columbus Circle, New York, NY 10023
Phone: (212) 801-1073
RMC-Related Management Company
60 Columbus Circle, New York, NY 10023
Phone: (212) 801-1073
Billing
Attn: Amanda Grisham, Regional Manager
Winter Garden Apartments
5708 Kingsbury Pl, St. Louis, MO 63112
Phone: (314) 361-7225
Email: WinterGardenApts@related.com
Winter Garden Apartments
5708 Kingsbury Pl, St. Louis, MO 63112
Phone: (314) 361-7225
Email: WinterGardenApts@related.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace hoist ropes within 30 days--red rouge & reduced diameter | 9/25/2018 |
| conversion | conversion | n/a | No | No | Post current State Certificate in machine room | 9/25/2018 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | perform monthly fire service and document on log in machine room | 11/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide complete maintenance control program and post on controller in machine room | 11/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures in the MCP on or by January 1 2022 | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Isolation pads need replacing | 8/16/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs cleaning | 8/16/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 8/16/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide a maintenance control program | 8/16/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | No | No | Patch holes in machine room floor by the entrance tripping hazard | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 8/10/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | replace missing electrical box cover for fan top of car | 8/16/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 12/5/2025 |
| A17.1-1996 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 1206.7 | Yes | Yes | Perform Monthly Fire Service Test and Document on Log Posted in the Machine room | 8/31/2026 |