Inspection
Inspection Details
Equipment ID
10662
10662
Inspection Date
12/22/2017
12/22/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
19f/12r
19f/12r
External ID
Location
US Bank- Chesterfield
1050 Woodsmill Rd, Chesterfield, MO
Phone: (636) 391-4212
1050 Woodsmill Rd, Chesterfield, MO
Phone: (636) 391-4212
Owner
US Bank- Chesterfield
15839 Manchester Rd, Ellisville, MO 63011
15839 Manchester Rd, Ellisville, MO 63011
Billing
Attn: US Bank
15839 Manchester Rd, , MO 63011
15839 Manchester Rd, , MO 63011
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Replace "roust-a-bout" oil supply pipe fittings with either cut, roll groove or threaded pipe fittings, in pit and equipment room. Re-insepction required. | 1/22/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair Alarm Bell - reinspection required | 1/22/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lighting. Bulb flickers on and off and it's not due to the bulb. | 12/31/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Rear car door will not stay open on Phase 2 fire service. Reinspect within 30 days. | 11/5/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | All automatic passenger elevators shall be provided with an alarm bell capable of being activated from inside the car & audible outside the hoistway | 12/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair inoperative emergency light and alarm. Re-inspection required | 1/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate shall be posted in the elevator machine room | 11/4/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Car door open per code on front door the rear car does not operate as required by code | 1/23/2024 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | Yes | No | Supply line has roustabout fittings which have been outlawed by code since 1984. replace fittings with victraulic or threaded pipe. | 1/23/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not work. Re-inspection required | 1/23/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not work. Re-inspection required | 1/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 11/4/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Rear door will not stay open on Phase 1 . Only elevator in the building, will allow 15 days to repair. Re-inspection required | 1/23/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | On phase 2 fire service, the rear door will not remain open at the 2nd floor, needs repaired. Re-inspection required | 12/31/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, needs repaired. Re-inspection required | 12/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | Yes | Yes | Elevator cab phone does not work, needs repaired. Red-tagged, Re-inspection required | 12/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | Yes | Yes | Elevator cab alarm bell does not work, needs repaired. Red-tagged, Re-inspection required | 12/31/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | No | Install phase 1 & 2 operating instructions at both fireman's operation key switches. Re-inspection required | 12/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work in the elevator cab. Repair or replace. Reinspection required | 11/4/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service could not be tested due to not having key. Key is unknown. Reinspect in 14 days | 11/4/2025 |