Inspection
Inspection Details
Equipment ID
19917
19917
Inspection Date
6/3/2026
6/3/2026
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tony Lesniak
Tony Lesniak
Mechanic Name
Michael Beachner
Michael Beachner
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
26
26
External ID
2e5b4d93-18ae-468b-b2ac-da13b2ede42e
2e5b4d93-18ae-468b-b2ac-da13b2ede42e
Location
Arrowhead Stadium
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
Owner
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Billing
Attn: Gregory Houser
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: GHouser@chiefs.nfl.com
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: GHouser@chiefs.nfl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | hoistway door identification numbering on the top two landings does not match the jamb braille, redo the door numbering to match the jamb braille | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | the top two floor are numbered 7 and 8 on the hoistway side while the jambs are numbered 8 and 9. change the hoistway number to match the jamb number to avioid confusion | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | repair top landing hoistway access keyswitch, it would not run the elevator in the down direction | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | adjust the door close to below 30lbf, measured over 35lbf | 5/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | the top two landing the hoistway side numbers do not match the jamb numbers, renumber the hoistway side to match the jamb numbers | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | repair the top landing hoistway access, could not run the elevator down | 7/28/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning. | 6/6/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | The Maintenance Control Program On-Site documents are not in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/28/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Did not have a written record of the maintenance performed on this elevator in the machine room. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide updated maintenance task log for 2026 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Repair emergency cab lighting | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | Provide proper counterweight runby - shorten hoist ropes | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Install car door restrictor brackets on long fascia runs in hoistway | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Install electrical box cover next to pit ladder - NEC code | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Repair/replace pit lighting |