Inspection
Inspection Details
Equipment ID
14580
14580
Inspection Date
12/19/2017
12/19/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
Location
Frisco Station Apartments
601 S Main St, Joplin, MO
Phone: (417) 782-1550
601 S Main St, Joplin, MO
Phone: (417) 782-1550
Owner
Frisco Station Apartments LP
205 W Walnut #200, Springfield, MO 65806
205 W Walnut #200, Springfield, MO 65806
Billing
Attn: Frisco Station Apartments
601 Main St, , MO 64801
601 Main St, , MO 64801
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Pit needs to be dry and clean--water in pit | 7/21/2018 |
| conversion | conversion | n/a | No | No | rusted conduit in pit needs to be replaced-water damage | 7/21/2018 |
| conversion | conversion | n/a | No | No | counterweight buffer switch needs to be cleaned | 7/21/2018 |
| conversion | conversion | n/a | No | No | pit channels rusted needs to be cleaned down and repainted-water damage | 7/21/2018 |
| conversion | conversion | n/a | No | No | a perminent sump pump be installed | 7/21/2018 |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 210.2(w) | Yes | No | Buffer switch not working 30 days to repair | 11/7/2018 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | machine room door needs new door lock | 3/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. | 3/31/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work and give proper location. | 10/20/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work and give proper location. | 10/20/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency Phone operable. 2.27 | 12/15/2022 |