Inspection
Inspection Details
Equipment ID
1872
1872
Inspection Date
2/20/2019
2/20/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
William Gorden, Jr.
William Gorden, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
6abdf6c3-2c7e-4166-898d-012f69878df5
6abdf6c3-2c7e-4166-898d-012f69878df5
Location
Ameren Missouri
1901 CHOUTEAU AVE, SAINT LOUIS, MO
1901 CHOUTEAU AVE, SAINT LOUIS, MO
Owner
Attn: Ameren
Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light not working. | 2/12/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. | 5/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 5/9/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 5/9/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | The stop switch in the elevator has degraded and does not operate properly. Repair or replace switch. | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not addressing its location properly. Check and repair the programming to give the proper location of this phone for passenger safety. Reinspection required. | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The elevator safety drum rope was replaced at some point in time with a non-code conforming material. Safety drum rope must be of a corrosion-resistant non ferrous material and not be of tiller rope construction. Reinspection and safety test is required. | 5/13/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 5/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not addressing its location properly. Check and repair the programming to give the proper location of this phone for passenger safety. Reinspection required. | 1/25/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | The elevator safety drum rope was replaced at some point in time with a non-code conforming material. Safety drum rope must be of a corrosion-resistant non ferrous material and not be of tiller rope construction. Reinspection and safety test is required. | 1/25/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Car safety mini drum cable is wrong type material, replace. | 1/28/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/9/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/9/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Provide machine room door to be self closing. | 11/19/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Provide pit light to work. | 11/19/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Door force exceeds 30#. Adjust as needed. | 11/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Worm shaft seal is worn and leaking. Repair or replace as needed. | 5/13/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The seismic detection operation of the elevator shall operate as designed. The elevator failed to recall to closest floor, open doors, and remain inoperable until reset by a licensed mechanic |