Inspection
Inspection Details
Equipment ID
1878
1878
Inspection Date
2/19/2019
2/19/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
fd525ada-1755-42dc-b0ae-832f8dac7027
fd525ada-1755-42dc-b0ae-832f8dac7027
Location
Ameren Missouri
1901 CHOUTEAU AVE, SAINT LOUIS, MO
1901 CHOUTEAU AVE, SAINT LOUIS, MO
Owner
Attn: Ameren
Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil recovery pump in pit which is for temporary use only. Replace with proper container to allow measurement of oil leakage. | 8/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform OSV test on or before next annual inspection date. | 8/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.4 Plunger Gripper Testing | No | No | Plunger gripper is not sealed. Perform test on or before next annual inspection date. | 8/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Car not working, repair as needed. Reinspect. | 1/23/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 8/21/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 12/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Sump hole has oil, remove. | 8/21/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Determine if the sump pump works, if not replace. | 8/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 8/21/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 12/4/2025 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 12/4/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone works, but goes to previous contractor. Reprogram. | 12/4/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone works, but goes to previous contractor. Reprogram. | 2/12/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | The visual/text communication for assisting passengers unable to communicate verbally or hear shall be operable. |