Inspection
Inspection Details
Equipment ID
16281
16281
Inspection Date
2/15/2019
2/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Barnhart
Michael Barnhart
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
367d4163-b25c-4c50-b621-889a709736e8
367d4163-b25c-4c50-b621-889a709736e8
Location
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO
1 RIVERBOAT DR, N KANSAS CITY, MO
Owner
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
Billing
Attn: Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post a log in the machine room | 7/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | missing hoistway door sight guard on the 4th floor | 5/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | replace the fire service phase 1 keyswitch collar, can not read the markings on the collar | 5/31/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | a new copy of the state operating certificate is to be posted in the machine room every year, the one on display is from 2014 | 5/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Adjust the door restrictor so it works | 5/31/2022 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 3.1 | No | No | Smoke damper at the top of the hoistway should be closed, and only open when the hoistway smoke detectors are activated (2.1.4) | 10/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor has been disabled, repair and adjust the door restrictor | 2/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Clean the unexposed hoistway sills and door equipment | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove oil from the catch pan beneath the power unit | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove oil from the catch pan beneath the power unit | 7/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide updated operating permit in the cab or other specified location | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | cab ceiling rib has been crushed in the center of the ceiling, the whole cab ceiling is bent in, repair or replace cab ceiling. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top after construction in the area is completed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | clean down hoistway and pit after construction in the area is completed. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Cab flooring has been removed creating a trip hazard at the sill, protect the car sill with ramp since new floor covering is not going to be installed until construction is completed. |