Inspection
Inspection Details
Equipment ID
17427
17427
Inspection Date
2/13/2019
2/13/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Christopher Bolin
Christopher Bolin
Relief Valve Pressure
440
440
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
12/14
12/14
External ID
3ac73fe2-d434-4d73-a312-6b51af1f8427
3ac73fe2-d434-4d73-a312-6b51af1f8427
Location
Harrahs Pavilion
10 RIVERBOAT DR, N KANSAS CITY, MO
10 RIVERBOAT DR, N KANSAS CITY, MO
Owner
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
Billing
Attn: Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
1 RIVERBOAT DR, N KANSAS CITY, MO 64116-3267
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | repair the front car door restrictor, the hook did not catch the latch | 7/21/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Perform monthly fire service test and post a log in the machine room | 7/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 12/6/2022 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | emergency light battery is dead, replace batteries and verify operation | 3/11/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | repair the phase 1 audible signal, it did not work | 3/11/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Repair the front door restrictor so that it works | 11/4/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Repair phase one keyswitch did not work, repair keyswitch | 11/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Recovery pump in the elevator pit for hydraulic oil not allowed per memo from the state, memo 006 (A17.1 8.6.5.5) | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Recovery pump in the elevator pit for hydraulic oil not allowed per memo from the state, memo 006 (A17.1 8.6.5.5) | 7/18/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | Fire service phase one recall audible signal did not work, repair audible signal | 2/2/2026 |