Inspection
Inspection Details
Equipment ID
14171
14171
Inspection Date
2/18/2019
2/18/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Jeffrey Dooley
Jeffrey Dooley
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
f61b933f-706d-4602-bc07-b7c02e99796e
f61b933f-706d-4602-bc07-b7c02e99796e
Location
Procter & Gamble
169 E GRAND AVE, SAINT LOUIS, MO
169 E GRAND AVE, SAINT LOUIS, MO
Owner
Procter & Gamble
169 E GRAND AVE, SAINT LOUIS, MO 63147-3213
169 E GRAND AVE, SAINT LOUIS, MO 63147-3213
Billing
Attn: Procter & Gamble
169 E GRAND AVE, SAINT LOUIS, MO 63147-3213
169 E GRAND AVE, SAINT LOUIS, MO 63147-3213
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | I1 Clean pit of oil and debris. | 4/24/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Remove standing oil in pit. | 4/24/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Provide maintenance records inside machine room. | 4/24/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean the oil off of machine room floor. | 4/24/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lights. | 4/24/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from the elevator pit. | 9/17/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Repair left side lower door panel gib. | 9/17/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Yes | No | Repair left side lower door panel gib, first floor. | 3/26/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Repair broken light guard on car top and remove broken glass | 2/23/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6 | 2/23/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove debris from pit. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. | 2/23/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Phase II Fire Fighters Operation is not functioning. |