Inspection
Inspection Details
Equipment ID
16894
16894
Inspection Date
2/20/2019
2/20/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
c297930b-cddf-4101-8003-99c060b2a7c0
c297930b-cddf-4101-8003-99c060b2a7c0
Location
St. Louis Busch Stadium
700 CLARK AVE, SAINT LOUIS, MO
700 CLARK AVE, SAINT LOUIS, MO
Owner
St. Louis Cardinals LLC
700 CLARK AVE, SAINT LOUIS, MO 63102-1727
700 CLARK AVE, SAINT LOUIS, MO 63102-1727
Billing
Attn: St. Louis Cardinals LLC
700 CLARK AVE, SAINT LOUIS, MO 63102-1727
700 CLARK AVE, SAINT LOUIS, MO 63102-1727
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install top inner deck card | 1/7/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Comb impact guides are rusted and need to be tested to insure proper impact calibration. | 2/20/2019 |
| conversion | conversion | n/a | No | No | Top left and bottom right end cap weather seal missing. | 1/7/2019 |
| conversion | conversion | n/a | No | No | Repair the bottom demarcation light | 1/7/2019 |
| A17.1-1996 : Escalators | 7.9 - Steps and upthrust device | 802.5 | No | No | Replace broken step demarcation strip. | 3/29/2023 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Clean escalator truss space. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 1206.6 | No | No | Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect within 30 days. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Both handrails are cracked. Need to be replaced. | 7/2/2020 |
| A17.1-1996 : Escalators | 7.16 - Ceiling intersection guards | 802.3g | No | No | Replace wrong ceiling intersection guards with correct ones. | 7/2/2020 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 802.6 | No | No | Replace broken step demarcations. | 7/2/2020 |
| A17.1-1996 : Escalators | 7.8 - Deck barricades and antislide devices | 802.3i | No | No | Missing deck barricades between the two escalators | 6/28/2022 |
| A17.1-1996 : Escalators | 8.4 - Drive machine and brake | 804 | Yes | Yes | Escalator brake torque when tested was at 115lbs, the maximum torque for this unit is 75lbs. Readjust brake torque to be within limits. No red tag issued at this time, reinspection is required. | 3/4/2024 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Top demarcation light fixture failed to illuminate, repair or replacement is required. | 8/26/2025 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 806 | No | No | The interior top “splash guard” is missing which prevents the accumulation of dirt and debris from entering electrical components. Reinstall splash guard to prevent damage to interior equipment. | 8/26/2025 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Top demarcation light fixture failed to illuminate, repair or replacement is required. | 8/26/2025 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 806 | No | No | The interior top “splash guard” is missing which prevents the accumulation of dirt and debris from entering electrical components. Reinstall splash guard to prevent damage to interior equipment. | 8/26/2025 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 806 | No | No | Top interior “splash guard” missing, replace. | 8/26/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Replace right side handrail | 8/26/2025 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.2 | No | No | Isolate vibration, determine cause ,and correct. | 8/26/2025 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 801.1 | No | No | Tighten main step chain | 8/26/2025 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Perform Annual clean down of Escalator | 8/26/2025 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.2 | No | No | Determine where loud squeaking noise is from and correct ASAP | 8/26/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Record maintenance, call backs, repairs, and testing in MCP and place location of MCP on Controller | 8/26/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4.1(d) | No | No | Record Step/Skirt Indexing Graph for 2025 in MCP | 8/26/2025 |