Inspection
Inspection Details
Equipment ID
10495
10495
Inspection Date
2/19/2019
2/19/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
David Tiemann
David Tiemann
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
27
27
External ID
01747c16-61e5-4f84-ba90-5970dd4c4143
01747c16-61e5-4f84-ba90-5970dd4c4143
Location
Tegler Hall
3550 LINDELL BLVD, SAINT LOUIS, MO
3550 LINDELL BLVD, SAINT LOUIS, MO
Owner
St. Louis University
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
Billing
Attn: St. Louis University
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
3500 LINDELL BLVD, SAINT LOUIS, MO 63103-1021
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are undersized, replacement required within 30 days. | 3/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Suspension ropes need to be shortened. There is only 3 inches of c-measurement, needs to be a minimum of 6". Re-inspection required | 4/12/2022 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties did not reach minimum amount of slide required for a 350 fpm car. Unit has been Red-Tagged, Re-inspection required | 4/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Suspension ropes needs to be shortened. There is only 3" of c-measurement, needs to be 6". Re-inspection required | 4/12/2022 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties did not reach minimum amount of slide required for 350 lb car. Unit is still red tagged | 4/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Replace BC fire extinguisher in machine room with a ABC fire extinguisher | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Shorten hoist cables, car not making it to the top final when the counterweight buffer is fully compressed | 1/8/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Elevator car door restrictor inoperable. Re-inspection required | 12/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Need to replace BC extinguisher in the elevator machine room with an ABC | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Need to shorten hoist cables, car not making it to the top final when counterweight buffer is fully compressed. Re-inspection required | 12/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Need to re-program emergency phone, it calls an inactive number. Re-inspection required | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Need to shorten hoist cables, car not making it to the top final when counterweight buffer is fully compressed. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor inoperable, needs to be repaired or replaced. Re-inspection required |