Inspection
Inspection Details
Equipment ID
5749
5749
Inspection Date
2/21/2019
2/21/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
750
750
Slide
1/2
1/2
Governor Rope Pull
5/100
5/100
Door Closing Force
12
12
External ID
456dc8b2-6441-4990-a0b8-d70708fc8fd1
456dc8b2-6441-4990-a0b8-d70708fc8fd1
Location
Midtown, LLC
3010 LOCUST ST # 3016, SAINT LOUIS, MO
3010 LOCUST ST # 3016, SAINT LOUIS, MO
Owner
Midtown Property, LLC
3010 LUSTO ST STE 100, ST. LOUIS, MO 63103
3010 LUSTO ST STE 100, ST. LOUIS, MO 63103
Billing
Attn: Midtown Property LLC
3010 LOCUST ST STE 100, SAINT LOUIS, MO 63103-1371
3010 LOCUST ST STE 100, SAINT LOUIS, MO 63103-1371
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Unsealed | 3/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Not working,repair as needed. | 4/10/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Overhead governor shall be tested for proper setting of safeties. Unable to test with one person. | 8/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | Lobby fire hat does not illuminate on phase 1 recall. | 8/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Phone does not work without 110v. | 8/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Spaces containing machines, control equipment, sheaves, and other machinery shall be separated from the remainder of the building by fire-resistive enclosure. | 5/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/27/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Replace missing in-car capacity plate. | 5/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Phone does not work when 110v circuit to car is disconnected. This violation was originally cited on 4/19/24 and still not corrected as of 8/15/24. This shall be corrected within 14 days or unit will be red tagged and placed out of service until corrected. | 10/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Relief valve pressure test shall be completed. Mechanic did not have proper gauge attachment to connect. | 5/1/2025 |