Inspection
Inspection Details
Equipment ID
9725
9725
Inspection Date
3/6/2019
3/6/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Paul Bartlett
Paul Bartlett
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
d3dde8ec-6dc4-4341-9a9f-831fb6287833
d3dde8ec-6dc4-4341-9a9f-831fb6287833
Location
Catholic Campus Ministries
847 S HOLLAND AVE, SPRINGFIELD, MO
847 S HOLLAND AVE, SPRINGFIELD, MO
Owner
Attn: Catholic Campus Ministries
Catholic Campus Ministries
847 S HOLLAND AVE, SPRINGFIELD, MO 65806
Phone: (417) 865-0802
Email: creichert@ccm847.org
Catholic Campus Ministries
847 S HOLLAND AVE, SPRINGFIELD, MO 65806
Phone: (417) 865-0802
Email: creichert@ccm847.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | telephone will not call out at all--suspect line-phone needs to go to 24 hr service | 3/6/2019 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 4/1/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating cert. in machine room. 5.100(2) | 4/1/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Must provide current annual test tag on mach. room fire extinguisher. 2.7 | 4/1/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Must provide and maintain MCP Doc. 8.6.1.2.1 | 4/1/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating Cert. in Mach room. 5.100(2) | 4/1/2023 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must perform Category 5 test/insp. for the overspeed valve on or before next annual insp. 8.6.5.16.5 | 4/1/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make emergency phone operable. 8.6.4.15 | 3/30/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Phone Operable. 8.6.4.15 | 7/17/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Must perform and document Cat 5 test for OSV (overspeed valve). 8.6.5.16.5 | 7/17/2024 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | must provide clear buckets to catch oil instead of drain tubes running back to the tank | 7/1/2025 |