Inspection
Inspection Details
Equipment ID
6073
6073
Inspection Date
2/26/2019
2/26/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
21
21
External ID
fd5f8235-2d86-49c3-8304-707ffabe0bb1
fd5f8235-2d86-49c3-8304-707ffabe0bb1
Location
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO
Owner
Attn: Rick Creviston
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO 63102
Phone: (314) 342-4660
Email: Rick.creviston@hyatt.com
Arch Hotel Project Owner LLC
N 4TH ST AT CHESTNUT ST, SAINT LOUIS, MO 63102
Phone: (314) 342-4660
Email: Rick.creviston@hyatt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Counterweight buffer is being compressed 1" when car is at top landing. Shorten suspension ropes to maintian proper counterweight runby. | 3/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | Traction machine leaking oil onto outboard side of drive sheave. Repair leaking seal. | 3/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | Yes | Emergency brake is not working due to oil leaking onto braking surface and brake pads. Elevator removed from service until repaired. | 3/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Counterweight buffer is being compressed 1" when car is at top landing. Shorten suspension ropes to maintain proper counterweight runby. | 2/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | Traction machine leaking oil onto outboard side of drive sheave. Repair leaking seal. | 2/23/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pits | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway door gibs on basement doors | 10/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Repair lighting above stairway accessing machine room to provide safe access for workers | 10/15/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. Repair same | 10/15/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Fire seal hoistway (corner) near floor 1. | 12/9/2025 |
| A17.1-2016 : Elevators | 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators | 2.27.1 | Yes | No | FEO Phase I and II need to be tested when hall risers are installed. | 12/9/2025 |