Inspection
Inspection Details
Equipment ID
8519
8519
Inspection Date
6/5/2017
6/5/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
Location
Fifth Third Center
8000 Maryland Ave, Clayton, MO
Phone: (314) 725-8333
8000 Maryland Ave, Clayton, MO
Phone: (314) 725-8333
Owner
Hoffmann International Commercial Real Estate
8000 Maryland Ave, Clayton, MO 63105
8000 Maryland Ave, Clayton, MO 63105
Billing
Attn: 8000 Maryland LLC
8000 Maryland Ave, Ste 1120, , MO 63105
8000 Maryland Ave, Ste 1120, , MO 63105
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Compensating chains needs to be shortened. | 6/12/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Need to perform brake, buffer, car & counterweight, safety slide testing. | 8/1/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) | 7/30/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Red tag issued: damaged hoistway ropes. Replace ropes and check driver for damaged grooves. | 9/5/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested. | 9/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current Mo state operating certificate ahll be posted in the elevator equipment room in a noncombustible frame with a clear protective vision place over it. | 12/22/2025 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.10.2.2.3(b) | No | No | The car top light shall be operational | 12/22/2025 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 Firefighters’ Emergency Operation | No | No | Firefighters phase one instructions shall be posted near the phase one keyswitch in the hallway at the egress floor. | 12/22/2025 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.10.2.2.3(b) | No | No | The electrical fitting on the car-top emergency exit switch is broken and shall be repaired or replaced. | 12/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Suspension ropes shall be shortened. | 9/1/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room floors, machinery, and control spaces shall be kept free of water, dirt, rubbish, oil, and grease. | 9/1/2026 |