Inspection
Inspection Details
Equipment ID
18286
18286
Inspection Date
2/27/2019
2/27/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
392c0f0b-0bc0-4f3b-9b9f-721c8c1d85ca
392c0f0b-0bc0-4f3b-9b9f-721c8c1d85ca
Location
Dicks Sporting Goods
200 W COUNTY CTR, DES PERES, MO
200 W COUNTY CTR, DES PERES, MO
Owner
Westfield- Dicks
44 W COUNTY CTR, DES PERES, MO 63131-3724
44 W COUNTY CTR, DES PERES, MO 63131-3724
Billing
Attn: Westfield- Dicks
80 W COUNTY CTR, DES PERES, MO 63131-3701
80 W COUNTY CTR, DES PERES, MO 63131-3701
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Left handrail is cracked. | 12/18/2020 |
| A17.1-1996 : Escalators | 7.9 - Steps and upthrust device | 802.6e | No | No | Replace broken step tread. | 12/18/2020 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.4 | No | No | Left handrail is cracked. Repair/replace handrail. | 12/18/2020 |
| A17.1-1996 : Escalators | 7.9 - Steps and upthrust device | 802.5 | No | No | Replace broken step treads. | 12/18/2020 |
| A17.1-1996 : Escalators | 7.8 - Deck barricades and antislide devices | 802.3i | No | No | Lower deck barricade not fastened. | 12/18/2020 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.3a | No | No | Warning buzzer on bottom stop switch cover does not work. | 12/18/2020 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1008.2a | No | No | Clean pits and drip pans. | 8/31/2022 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.15.19 | No | No | Failed index test | 8/31/2022 |
| A17.1-1996 : Escalators | 8.13 - Handrail systems and safety devices | 802.4 | No | No | The handrail inlet at the top landing to the left skirting has degraded to the degree that replacement is required. | 12/10/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Provide unit clean down. | 12/10/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Hand rail (l) is cracked, replace. | 12/10/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.7 Rollers, Tracks, and Chains | Yes | No | Hand rail drive chain needs adjustment. Provide. | 3/3/2026 |