Inspection
Inspection Details
Equipment ID
10702
10702
Inspection Date
2/27/2019
2/27/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
11"
11"
Governor Rope Pull
180/460
180/460
Door Closing Force
24/20
24/20
External ID
2d7d0e54-11bf-40c7-aed7-ad3c481dd32c
2d7d0e54-11bf-40c7-aed7-ad3c481dd32c
Location
Parkview Elderly Apts
4451 FOREST PARK AVE, SAINT LOUIS, MO
Phone: (314) 533-3350
4451 FOREST PARK AVE, SAINT LOUIS, MO
Phone: (314) 533-3350
Owner
Attn: Sontez Singleton
The Habitat Company
4451 FOREST PARK AVE, SAINT LOUIS, MO 63108
Phone: (314) 533-3350
Email: ssingleton@habitat.com
The Habitat Company
4451 FOREST PARK AVE, SAINT LOUIS, MO 63108
Phone: (314) 533-3350
Email: ssingleton@habitat.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency bell does not work | 2/7/2019 |
| conversion | conversion | n/a | No | No | Pits shall be clean | 5/9/2019 |
| MO Minimum : Elevators | (E) - Machines | (E)1 | No | No | Repair or replace machine drive sheave. | 5/9/2019 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Replace contaminated machine brake shoes. | 2/27/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Car door restrictor does not work. | 5/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work on battery back-up. | 5/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site for each elevator. | 6/7/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program not on site | 6/7/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pits shall be kept dry, clean & free of equipment or material not relating to the operation of the elevator | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A MCP shall be kept for each unit and kept on site | 3/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Rear car door restrictor does not work. Repair | 1/5/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has trash and debris in it. Clean elevator pit | 3/27/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Top of hoistway smoke needs to be programmed correctly to go to primary floor. | 10/18/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Only one smoke detector in the shared machine room for all three elevators. Provide additional smoke detectors to achieve proper coverage. | 10/18/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | All three elevators will have emergency generator power. Emergency power shall be tested once modernizations are complete. | 10/18/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Provide additional relay to separate the shunt trip function between the 2 hoistways. Shunt to only activate when heat detector in the respective hoistway is triggered. | 10/18/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Phone monitoring will be added to duplex lobby. When all three are completed, push button station must be checked. | 10/18/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | All three elevators will have emergency generator power. Emergency power shall be tested once modernizations are complete. | 5/27/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Phone monitoring will be added to duplex lobby. When all three are completed, push button station must be checked. | 5/27/2025 |