Inspection
Inspection Details
Equipment ID
12597
12597
Inspection Date
2/27/2019
2/27/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
John Wiesehan
John Wiesehan
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
ea3dc38d-f32c-40a1-94ff-b3a9f27eb8ad
ea3dc38d-f32c-40a1-94ff-b3a9f27eb8ad
Location
Gateway One
701 MARKET ST STE 1230, SAINT LOUIS, MO
701 MARKET ST STE 1230, SAINT LOUIS, MO
Owner
Attn: Gateway One
Gateway One
701 MARKET ST STE 1230, SAINT LOUIS, MO 63101
Phone: (314) 241-1245
Email: peabodyplaza@colliers.com
Gateway One
701 MARKET ST STE 1230, SAINT LOUIS, MO 63101
Phone: (314) 241-1245
Email: peabodyplaza@colliers.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to. | 11/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 5/16/2024 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to. | 11/16/2025 | ||
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | x | Machine room door shall be self-closing and self-locking. | 5/28/2024 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Disconnect breaker jams, not allowing for proper opening of mainline circuit. | 5/28/2024 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Disconnects does not have 36" workspace clearance to nearest object (air handler). | 5/28/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power must be tested. | 5/28/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power must be tested. | 11/16/2025 | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | Car top shall be cleaned. | 2/8/2026 | ||
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | Car top shall be cleaned |