Inspection
Inspection Details
Equipment ID
13634
13634
Inspection Date
2/27/2019
2/27/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
John Wiesehan
John Wiesehan
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
27
27
External ID
36bfc100-0860-4bac-8992-1974ce2bc9af
36bfc100-0860-4bac-8992-1974ce2bc9af
Location
Gateway One
701 MARKET ST STE 1230, SAINT LOUIS, MO
701 MARKET ST STE 1230, SAINT LOUIS, MO
Owner
Attn: Gateway One
Gateway One
701 MARKET ST STE 1230, SAINT LOUIS, MO 63101
Phone: (314) 241-1245
Email: peabodyplaza@colliers.com
Gateway One
701 MARKET ST STE 1230, SAINT LOUIS, MO 63101
Phone: (314) 241-1245
Email: peabodyplaza@colliers.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to. | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | A number of guide rollers have degraded to the point of replacement is required on the elevator car and counterweight. Replace the degraded rollers. | 11/16/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to. | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Elevator hoisting ropes need to be shortened in order to meet the minimum requirement runby of 6” | 8/10/2022 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties are stopping the car with a 9” slide with a 6” shoe, making the slide only 3”. The minimum stopping distance for the car is 13” after the shoe is subtracted from the actual slide | 8/10/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Testing is incomplete and must have the counterweight slide checked and do fire service | 8/10/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work on 110v emergency power. Repair or replace | 8/10/2022 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties are stopping the car with a 9" slide with a 6" shoe, making the slide only 3". The minimum stopping distance for the car is 13" after the shoe is subtracted from the actual slide. Red- Tagged, Re-inspection required | 8/29/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing is incomplete and mush have the counterweight slide checked and do fire service. Re-inspection required. | 8/29/2022 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)4 | Yes | Yes | /car safeties are stopping the car with a 9" slide with a 6" shoe, making the slide only 3". The minimum stopping distance for the car is 13" after the show is subtracted from the actual slide. Red tagged, Re-inspection required | 9/23/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing is incomplete and must have the counterweight slide checked and do fire service. Re-inspection required | 9/23/2022 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Main and lighting disconnects need feed location labels. | 11/16/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | All units to be tested on emergency power. | 11/16/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | All FAID to be tested for all units together, reconfigured for current grouping and fire status panel. | 11/16/2025 |
| A17.1-2016 : Elevators | 5.5 - Traveling cables | 2.8.2 | Yes | No | Traveling Cable is damaged and shall be replaced | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be cleaned |