MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
In car stop switch (RH) shall work.
|
1/20/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
|
11/16/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
|
11/16/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
The signage for “In Case of Fire” is missing. Install signage that conforms to the building code this elevator was installed to conform to.
|
11/16/2025
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
No
|
No
|
There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to.
|
11/16/2025
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
Yes
|
No
|
Pull type stop switch in car did not emergency alarm system while in fire service. Repair or replace
|
4/16/2024
|
|
A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.10.2.3 Toe Board
|
Yes
|
No
|
Install toe kick on upper deck guard rail.
|
11/16/2025
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
Yes
|
No
|
Machine room shall have GFCI outlet. Currently standard outlets.
|
11/16/2025
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Emergency power operation to be tested before project completion.
|
11/16/2025
|