Inspection
Inspection Details
Equipment ID
6888
6888
Inspection Date
2/14/2019
2/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
c1ee2ad9-818c-41b6-bd36-08a7659efbd5
c1ee2ad9-818c-41b6-bd36-08a7659efbd5
Location
The Randolph
5510 WATERMAN BLVD, SAINT LOUIS, MO
5510 WATERMAN BLVD, SAINT LOUIS, MO
Owner
Attn: UNK
Oxford Condominium Associaction c/o Lechner Realty Group Management, LLC
13421 Manchester Road Suite 101, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Oxford Condominium Associaction c/o Lechner Realty Group Management, LLC
13421 Manchester Road Suite 101, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Install anti-rotation device on the counterweight shackles. | 9/10/2020 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/10/2020 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 9/10/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide a code compliant MCP including onsite documents. | 1/31/2023 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be displayed in the elevator machine room. | 1/31/2023 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 3/15/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | The fire extinguisher shall be up to date. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | |||
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | The pit light shall be operational. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | x | Two of the four shackle springs are broken on the counterweight, causing uneven rope tension. Replace broken springs (recommend replacing all four springs as they are all the same age). | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Means of access to machine room shall be of a permanent nature and shall be constructed and maintained in a clear and unobstructed manner. Currently, personnel must cross roof, climb up and over an approximately 42" high part of building and back down the other side to reach the machine room. There are no ladders or railing protecting persons from fall hazard on the side of this part of roof. Note: If this violation is not corrected at the time of the next annual inspection, a re-inspection will be required. |