Inspection
Inspection Details
Equipment ID
15303
15303
Inspection Date
3/8/2019
3/8/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
19
19
Governor Rope Pull
90/500
90/500
Door Closing Force
26
26
External ID
197fd801-d041-4fbb-a74c-57557740bbc3
197fd801-d041-4fbb-a74c-57557740bbc3
Location
Lindell Towers West
3745 LINDELL BLVD, SAINT LOUIS, MO
3745 LINDELL BLVD, SAINT LOUIS, MO
Owner
Attn: St Louis Properties
St Louis Properties
3701 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (918) 575-0716
Email: cm@coronadoplaceandtowers.com
St Louis Properties
3701 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (918) 575-0716
Email: cm@coronadoplaceandtowers.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Water standing in pit, remove. Sump pump most likely not working. | 4/3/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | Prove safe access to machine room. Relamp landing lights as needed | 4/3/2026 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Provide code compliant machine room lighting | 4/3/2026 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | Provide safe access to machine room, replace burnt out bulbs | 4/3/2026 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Provide code compliant machine room lighting | 4/3/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | There is standing water in pit, sump pump isn't working | 4/3/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 4/3/2026 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | No | No | The gap between the door and the cop exceeds 10 mm. Re-inspection required | 4/3/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light does not work | 4/3/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | Counterweight runby shall not be less than 6". Currently 4". | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | There is standing water in pit, sump pump isn't working. Pit shall be kept dry. Repair Sump, Clean pit, remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lighting needs to be repaired, 1 or more bulbs not working. | |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | No | No | The gap between the door and the cop exceeds 10 mm. | |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Hoist Rope Tail retaining clips shall be properly spaced (car side) | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light shall work | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire Service testing must be properly documented monthly on Log Sheet located in the MCP. No Log present. | |
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 102 | No | No | Cab Lighting cartop wiring box is missing cover, wires hanging out. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Items to be completed: 100% Safety Set, Slide, 125% items. |