Inspection
Inspection Details
Equipment ID
8613
8613
Inspection Date
3/18/2019
3/18/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Bobby Joe Mehrens
Bobby Joe Mehrens
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
47be49e5-f9c8-47c3-871b-21a29f063634
47be49e5-f9c8-47c3-871b-21a29f063634
Location
Commerce Bank- St. Joseph
3303 ASHLAND AVE, SAINT JOSEPH, MO
3303 ASHLAND AVE, SAINT JOSEPH, MO
Owner
Commerce Bank- St. Joseph
328 FELIX ST, SAINT JOSEPH, MO 64501-2137
328 FELIX ST, SAINT JOSEPH, MO 64501-2137
Billing
Attn: Commerce Bank- St. Joseph
328 FELIX ST, SAINT JOSEPH, MO 64501-2137
328 FELIX ST, SAINT JOSEPH, MO 64501-2137
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Keep up to date wiring diagrams in the machine room. The wiring diagrams on site are not the correct ones for the elevator. | 6/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 6/1/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Install smoke sensing devices at elevator lobbies except the main designated landing. The smoke sensing devices, when activated, shall return elevator to the main designated landing. | 6/13/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Fire initiating devices have been installed but need to be tested with an inspector present. | 6/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Remove newly installed fire initiating device at the main landing. Per A17.1-1978 rule 211.3a2 | 6/16/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove non-elevator related material from machine room. (Gallons of paint-water hose-water sprinkler-snow shovel) | 6/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone dials out but does not connect. | 6/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Keep the correct and up to date wiring diagrams for the elevator in the machine room. | 6/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 6/20/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | No audible signal during fire recall | 6/20/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water accumulated in the elevator pit from the broken water line from the drinking fountain shall be removed. | 3/12/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone didnt work |