Inspection
Inspection Details
Equipment ID
7523
7523
Inspection Date
3/20/2019
3/20/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
George Riche
George Riche
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
fc95c21a-ba9a-4c84-a03c-df9f0fdd197f
fc95c21a-ba9a-4c84-a03c-df9f0fdd197f
Location
Sullivan County Courthouse
109 N MAIN ST, MILAN, MO
109 N MAIN ST, MILAN, MO
Owner
Sullivan County
109 N MAIN ST, MILAN, MO 63556-1369
109 N MAIN ST, MILAN, MO 63556-1369
Billing
Attn: Sullivan County Clerk
109 N MAIN ST, MILAN, MO 63556-1369
109 N MAIN ST, MILAN, MO 63556-1369
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Phone inside elevator does not operate. | 6/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car door restrictor does not operate. | 6/16/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove standing water from elevator pit. Pits need to be kept clean and dry. | 4/20/2020 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Ref 8.6.5.5.1 Jack packing needs replaced. | 3/3/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Elevator Pit Sump Pump has stopped working, water accumulating in the elevator pit. Replace Pump. | 3/3/2023 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | The Cylinder Piston is carrying excessive oil needs Jack packing replaced. 2nd year violation. | 3/3/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating Certificate not available due to 2021 violation not corrected. | 3/26/2024 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | 93 NEC requires duplex FGCI in Elevator pit with a Single Non GFCI allow for sump pump. | 3/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current Operating Certificate not available. | 3/26/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | phase 1 recall indicator not lighting Buzzer works fine |