Inspection
Inspection Details
Equipment ID
888
888
Inspection Date
1/12/2018
1/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
Location
Senate Garage
201 W High St, Jefferson City, MO
Phone: (573) 522-2514
201 W High St, Jefferson City, MO
Phone: (573) 522-2514
Owner
State of MO- Senate Garage
301 W High St, Room 590, Jefferson City, MO 65102
301 W High St, Room 590, Jefferson City, MO 65102
Billing
Attn: OA- FMDC- RM- 730
PO BOX 809, , MO 65102
PO BOX 809, , MO 65102
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Needs a pit light. | 1/25/2023 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | x | Needs a pit ladder. | 1/25/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Provide an HVAC system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2 | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide an MCP in machine room to log maintenance, repairs, and inspections. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Provide guarding for lighting above drive machine in machine room. 2.7.5.1 | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | Provide a GFCI outlet in machine room. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | Main line disconnect not labeled with feed source. 2.26.4.1 | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | Car light disconnect not labeled with feed source. 2.26.4.1 | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | |||
MO Minimum : Elevators | (I) - Pits | (I)8 | Provide a cover for sump pump in machine room/pit. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Provide and HVAV system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2 | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Provide feed source for main line disconnect. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Provide feed source for cab light disconnect. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | Provide a GFCI outlet in machine room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Shorten ropes. | 12/17/2024 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide guarding for lighting above machine. | |||
MO Minimum : Elevators | (I) - Pits | (I)5 | Secure pit ladder. | |||
A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.19.3 | x | Adjust governor rope tension device in pit. | 12/17/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Provide an HVAC system in machine room to keep equipment within safe operating ranges. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | Provide a GFCI service outlet in machine room. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Provide guarding for lighting above drive machine in machine room. 2.7.5.1 | |||
MO Minimum : Elevators | (I) - Pits | (I)8 | Provide a cover for sump pump in machine room/pit. |