Inspection
Inspection Details
Equipment ID
19735
19735
Inspection Date
3/25/2019
3/25/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
Slide
12"
12"
Governor Rope Pull
250/950
250/950
Door Closing Force
24
24
External ID
6357c99c-fd36-45bb-ab11-7c019ec8528e
6357c99c-fd36-45bb-ab11-7c019ec8528e
Location
Main Street Place
501 S MAIN ST, JOPLIN, MO
501 S MAIN ST, JOPLIN, MO
Owner
Matt Miller Companies
413 S JEFFERSON AVE, SPRINGFIELD, MO 65806-2315
413 S JEFFERSON AVE, SPRINGFIELD, MO 65806-2315
Billing
Attn: Matt Miller Companies
431 S JEFFERSON AVE, SPRINGFIELD, MO 65806-2325
431 S JEFFERSON AVE, SPRINGFIELD, MO 65806-2325
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | x | 3.6& 5.4--up final does not work | 4/3/2019 | |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | x | x | governor tripping to high governor needs to be recaliberated | 4/3/2019 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | x | 1.2-Stop at rear of cab needsa to work properly | 4/3/2019 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | cab flooring needs to be permanently attached to sub floor and hole for safety key | 4/24/2019 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | cab lights needs to be protected by grill | 4/24/2019 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | 1.6 telephone has no signal--line is disconnected | 4/3/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | 8.6.1.6.5 fire extinguisher hasn,t been checked since 2016 | 4/24/2019 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | 2.4.2.1--suspension ropes need to be shortened | 4/3/2019 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | Each hoistway landing in any elevator hoistway shall be provided with a properly working door or gate | 4/24/2019 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | needs current certificate posted in machine room | 4/24/2019 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | 1.4 cab flooring needs to be permanently attached to sub floor with hole for safety key (tripping hazard) | 4/24/2019 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | 1.5--cab lighting needs to be protected by a grill | 4/24/2019 | ||
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | 1.6 telephone has no dial tone--telephone needs to be connected to a 24 hour service on a direct line | 4/24/2019 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | 8.6.1.6.5 fire extinguisher hasn't been checked since 2016 | 4/24/2019 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | 4.2 2nd floor hoistway door needs to be repaired and put back in service ( at present the floor buttons are disconnected and door is bolted shut | 4/24/2019 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | needs current certificate displayed in the machine room | 6/21/2019 |