Inspection
Inspection Details
Equipment ID
6920
6920
Inspection Date
1/3/2018
1/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
Location
St. Louis Marriott West
660 Maryville Centre Dr, Town & County, MO
Phone: (314) 878-2747
660 Maryville Centre Dr, Town & County, MO
Phone: (314) 878-2747
Owner
PMO III, LLC
660 Maryville Centre Dr, Town & Country, MO 63141
660 Maryville Centre Dr, Town & Country, MO 63141
Billing
Attn: St. Louis Marriott West
660 Maryville Centre Dr, , MO 63141
660 Maryville Centre Dr, , MO 63141
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean elevator car top. | 1/27/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair car door restrictor | 8/8/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate. | 1/27/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | No monthly fire log. | 1/27/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes need to be shortened. 15 days to complete repair and reinspect. | 2/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair broken Greenfield to top of car exit switch. | 10/19/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated operating certificate in machine room. | 10/19/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room shall be kept clean. | 10/19/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/11/2024 |
| A17.1-2016 : Elevators | 2.25 - Traction sheaves | 8.6.4.20.10 Braking System, Traction, and Traction Limits (Re-Inspection) | Yes | Yes | When performing the 5 year test, the car is loaded with 125% of the rated load. This requires testing to ensure that the car will safely stop and hold the load with the car leveled with the floor. During testing the traction sheave slipped and failed the 125% test. The elevator is placed out of service and a repair/reinspection shall be performed before the elevator is returned to operation. | 4/9/2024 |