Inspection
Inspection Details
Equipment ID
11074
11074
Inspection Date
3/14/2019
3/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
fdc82602-e739-47b1-b705-a27fa9de66cc
fdc82602-e739-47b1-b705-a27fa9de66cc
Location
St. Louis Chinese Christian Church
832 N WOODS MILL RD, CHESTERFIELD, MO
832 N WOODS MILL RD, CHESTERFIELD, MO
Owner
St. Louis Chinese Christian Church
832 N WOODS MILL RD, CHESTERFIELD, MO 63017-3215
832 N WOODS MILL RD, CHESTERFIELD, MO 63017-3215
Billing
Attn: St. Louis Chinese Christian Church
832 N WOODS MILL RD, CHESTERFIELD, MO 63017-3215
832 N WOODS MILL RD, CHESTERFIELD, MO 63017-3215
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Existing battery lowering unit does not work. | 3/2/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform test on or before next annual inspection. | 3/10/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 3/10/2025 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | Unsealed. | 4/7/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Battery backup lowering unit not working, repair as needed. | 4/7/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit (oil). | 3/10/2025 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Packing is worn and leaking, repair as needed. | 4/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display update Missouri Operating Certificate in machine room | 3/10/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean pit (oil) | 3/10/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Failed Cat 1 Standby power test. Re-inspection required | 9/26/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/10/2025 |