Inspection
Inspection Details
Equipment ID
2082
2082
Inspection Date
3/26/2019
3/26/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Relief Valve Pressure
525
525
Slide
Governor Rope Pull
Door Closing Force
f-17 r-18
f-17 r-18
External ID
4bbeb9c8-c23a-4990-9de9-be34c9082dbc
4bbeb9c8-c23a-4990-9de9-be34c9082dbc
Location
Rediscover Administration
1547 NE RICE RD, LEES SUMMIT, MO
1547 NE RICE RD, LEES SUMMIT, MO
Owner
Rediscover Administration
1555 NE RICE RD, LEES SUMMIT, MO 64086-6034
1555 NE RICE RD, LEES SUMMIT, MO 64086-6034
Billing
Attn: Rediscover Administration
1555 NE RICE RD, LEES SUMMIT, MO 64086-6034
1555 NE RICE RD, LEES SUMMIT, MO 64086-6034
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit has water an oil standing in it | 5/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emg. phone not working | 1/11/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt of operation displayed | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. | 1/19/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit floor, standing oil. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Mach room door is defeatable | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | mach room has non elev. related materials stored in it | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit floor has oil covering it clean same | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emg phone not working | 1/9/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door is defeatable needs to be made undefeatable | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil covering pit floor | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed |