Inspection
Inspection Details
Equipment ID
11252
11252
Inspection Date
3/27/2019
3/27/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Michael Barnhart
Michael Barnhart
Relief Valve Pressure
525
525
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
46a2c28e-8b42-4ff6-aaed-8e40645c3203
46a2c28e-8b42-4ff6-aaed-8e40645c3203
Location
Vintage Gardens
3310 N WOODBINE RD, SAINT JOSEPH, MO
3310 N WOODBINE RD, SAINT JOSEPH, MO
Owner
Vintage Gardens
3310 N WOODBINE RD, SAINT JOSEPH, MO 64505-9323
3310 N WOODBINE RD, SAINT JOSEPH, MO 64505-9323
Billing
Attn: Vintage Gardens
3310 N WOODBINE RD, SAINT JOSEPH, MO 64505-9323
3310 N WOODBINE RD, SAINT JOSEPH, MO 64505-9323
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Fire service hat lens on car operating panel has been knocked out and is missing. | 8/19/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need to identify unmarked floor lockout keyswitch located on car operating panel. | 8/26/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Elevator machine room door needs to be self locking. | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door unlocking rollers are missing on 1st and 2nd floor hoistway doors. | 8/19/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need to identify floor lockout keyswitch on car operating panel to corresponding car call that it locks out. | 8/26/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door needs to be non-defeatable and self locking. | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Replace missing hoistway door unlocking rollers on first and second floor. | 3/1/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No documentation of maintenance or testing in on site maintenance record log. | 7/15/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(c)(5) | No | No | Written checkout procedure for overspeed valve not on site. Needs to be kept in machine room. | 7/15/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 7/15/2022 |
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 212 | No | No | INSTALL LOCK NUTS ON DEAD END OF CABLES IN HOISTWAY OVERHEAD | 7/16/2025 |