Inspection
Inspection Details
Equipment ID
24485
24485
Inspection Date
3/14/2019
3/14/2019
Inspection Type
New Installation
New Installation
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Casey Collins
Casey Collins
Relief Valve Pressure
1250
1250
Slide
1/2
1/2
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
a879804d-9f2a-419f-9828-6d007bdec121
a879804d-9f2a-419f-9828-6d007bdec121
Location
Windsor High School
949 Windsor Harbor Road, Imperial, MO
Phone: (000) 000-0000
949 Windsor Harbor Road, Imperial, MO
Phone: (000) 000-0000
Owner
Attn: Windsor C-1 School District
Windsor C-1 School District
6208 US HIGHWAY 61 67, IMPERIAL, MO 63052
Phone: (636) 464-4461
Email: dcalbreath@windsor.k12.mo.us
Windsor C-1 School District
6208 US HIGHWAY 61 67, IMPERIAL, MO 63052
Phone: (636) 464-4461
Email: dcalbreath@windsor.k12.mo.us
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide phone line for emergency two-way communication. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | x | Install fire rated door on the elevator machine room. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | x | Change receptacles in machine room to GFIC | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | Install fire extinguisher in elevator machine room. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Install shunt trip disconnect in the elevator machine room. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.13.1 | x | Install floor covering and handrail in elevator cab. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.3.4 | x | x | Install smoke detectors for fire recall and program. | 7/12/2019 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.26.2.7 | x | Install single 110v receptacle in pit for sump pump. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | x | Install car buffers or bumpers. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 8/26/2019 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete due to roller broke on sling. Need to perform the following tests to complete inspection: Test safeties, phone, emergency lights & bell, OSV, cartop, & door restrictor. Re-inspection required | 3/31/2025 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Inspection incomplete. The OSV still needs to be tested. The elevator quit running during inspection |