Inspection
Inspection Details
Equipment ID
10501
10501
Inspection Date
3/28/2019
3/28/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Terry Hodges
Terry Hodges
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
a9f34f50-bcbf-47dd-a182-fe6c2654e777
a9f34f50-bcbf-47dd-a182-fe6c2654e777
Location
Lamplighter Inn North
2820 N GLENSTONE AVE, SPRINGFIELD, MO
2820 N GLENSTONE AVE, SPRINGFIELD, MO
Owner
Attn: UNK
Lamplighter Inn North
2820 N GLENSTONE AVE, SPRINGFIELD, MO 65803
Phone: (000) 000-0000
Lamplighter Inn North
2820 N GLENSTONE AVE, SPRINGFIELD, MO 65803
Phone: (000) 000-0000
Billing
Attn: Lamplighter Inn North
Lamplighter Inn North
2820 N GLENSTONE AVE, SPRINGFIELD, MO 65803
Phone: (000) 000-0000
Email: latricia@lamplighterhotels.com
Lamplighter Inn North
2820 N GLENSTONE AVE, SPRINGFIELD, MO 65803
Phone: (000) 000-0000
Email: latricia@lamplighterhotels.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Povide a light switch in the pit accessable to the lowest landing door. | 7/31/2018 |
| conversion | conversion | n/a | No | No | Enclose the elevator equipment with a 6 foot high chain link fence with a self closing self latching gate with a lock always locked outside never locked inside. maintain a minimum of 36 inches clear working splace around the equipment. | 7/31/2018 |
| conversion | conversion | n/a | No | No | Provide a capacity plate in the car. stating 2000 lb. capacity. | 7/31/2018 |
| conversion | conversion | n/a | No | No | Clean the machine spaace of combustibles, ie leaves, wood etc. anso the pit is very dirty and needs cleaned | 7/31/2018 |
| conversion | conversion | n/a | No | No | Replace the burnt out lights in the machine room | 7/31/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. This was on last years inspection too. | 5/21/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Provide a chainlink fence seperating the machine room from the other equipment serving the building not pretaining to the operation of the elevator | 5/21/2020 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.11.3.1.2(h) | No | No | Pump unit oil pan required to be pumped out | 2/14/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | No Records | 2/14/2022 |
| A17.1-2016 : Elevators | 2.9 - Guarding of exposed auxiliary equipment | 8.11.3.1.2(l) | No | No | Install proper cover for pump & motor | 2/14/2022 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | No | No | Jack seal needs to be replaced | 2/14/2022 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Cab lighting circuit being used to supply power door reopen device (NEC 620.22) | 4/5/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Alarm operable. 1.6 | 6/5/2024 |