Inspection
Inspection Details
Equipment ID
11150
11150
Inspection Date
3/8/2019
3/8/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Matthew Martin
Matthew Martin
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
7d2be7c6-dbc5-4db9-83a0-adf7d17214b2
7d2be7c6-dbc5-4db9-83a0-adf7d17214b2
Location
Midwest Medical Supply
13400 LAKEFRONT DR, EARTH CITY, MO
13400 LAKEFRONT DR, EARTH CITY, MO
Owner
KC LLC
13400 LAKEFRONT DR, EARTH CITY, MO 63045-1516
13400 LAKEFRONT DR, EARTH CITY, MO 63045-1516
Billing
Attn: KC LLC
13400 LAKEFRONT DR, EARTH CITY, MO 63045-1516
13400 LAKEFRONT DR, EARTH CITY, MO 63045-1516
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/2/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The emergency exit switch shall be operational. | 7/29/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Plunger is leaking excessive oil. | 7/24/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Battery lowering shall work. Take corrective action and re-test. | 5/19/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lighting - All lamps shall work. | 5/19/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired. It currently flickers severely. | 5/19/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 5/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly, need to repair phone line. Re-inspection required |