Inspection
Inspection Details
Equipment ID
7171
7171
Inspection Date
3/21/2019
3/21/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Glen Kuehner
Glen Kuehner
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
acbdf38d-82f7-4a48-b5cc-250ea47524f6
acbdf38d-82f7-4a48-b5cc-250ea47524f6
Location
Washington Ave Apts
1133 WASHINGTON AVE, SAINT LOUIS, MO
1133 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Washington Avenue Apartments
1133 WASHINGTON AVE, SAINT LOUIS, MO 63101-1102
1133 WASHINGTON AVE, SAINT LOUIS, MO 63101-1102
Billing
Attn: Washington Avenue Apartments
1133 WASHINGTON AVE, SAINT LOUIS, MO 63101-1102
1133 WASHINGTON AVE, SAINT LOUIS, MO 63101-1102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Install guard on light top of car | 2/7/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Repair pit light | 2/7/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Repair Fire Service Visual Signage in car | 3/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | No | No | Repair Emergency Light & Bell in car | 2/7/2019 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | Yes | No | Call cancel on fire service phase II is not working correctly. Re-inspection required | 10/25/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 3/14/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 11/19/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 4/21/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 6/4/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required. | 9/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Failed Category 1 Standby Power Test, Reinspection required. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing is overdue, recommend performing category 5 test and reinspection of emergency power together on the next inspection. |