Inspection
Inspection Details
Equipment ID
14508
14508
Inspection Date
3/29/2019
3/29/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Ryan Bollinger
Ryan Bollinger
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
FR 25 R 25
FR 25 R 25
External ID
c491aba4-38a0-4676-8f83-0ecc4d3f6502
c491aba4-38a0-4676-8f83-0ecc4d3f6502
Location
Nevada Regional Medical Center
800 S ASH ST, NEVADA, MO
800 S ASH ST, NEVADA, MO
Owner
Nevada Regional Medical Center
800 S ASH ST, NEVADA, MO 64772-3224
800 S ASH ST, NEVADA, MO 64772-3224
Billing
Attn: Nevada Regional Medical Center
800 S ASH ST, NEVADA, MO 64772-3224
800 S ASH ST, NEVADA, MO 64772-3224
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | needs record of oil loss | 2/21/2020 |
| conversion | conversion | n/a | No | No | front and rear door restrictor needs adjusted or repaired | 2/21/2020 |
| conversion | conversion | n/a | No | No | needs maintance on site | 2/21/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted | 2/21/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | No Records | 1/11/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must perform Category 5 Test for Overspeed Valve on or before next annual insp. 8.6.16.5 | 1/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current operating cert. in Mach room. 5.100(2) | 1/23/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Must Preform Cat 5 Full load test/insp for Overspeed Valve 90 days to correct. 8.6.5.16.5 | 9/18/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Phone operable. 8.6.4.15 | 9/18/2025 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | Must repir/replace jack packing gland to limit oil loss. ( pit overflow bucket was full and had been emptied in last 30 days.) 8.6.5.5 | 5/29/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit must be kept free of oil. 8.6.4.7 | 5/29/2026 |