Inspection
Inspection Details
Equipment ID
19379
19379
Inspection Date
1/8/2018
1/8/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
Location
Saggar Holdings
916 Olive, St. Louis, MO
Phone: (314) 650-6045
916 Olive, St. Louis, MO
Phone: (314) 650-6045
Owner
Saggar Holdings
916 Olive, St. Louis, MO 63101
916 Olive, St. Louis, MO 63101
Billing
Attn: Saggar Holdings
916 Olive, , MO 63101
916 Olive, , MO 63101
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Wiring not related to the function of the elevator shall not be run through elevator hoistway. | |
| conversion | conversion | conversion - reinspect | Yes | No | The existing cab emergency telephone does not work and shall be repaired and tested. | 11/21/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | All the holes in the hoistway shall be sealed. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the upper pit of dirt and debris. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | Remove abandoned piping from the hoistway. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Wiring at the top of the hoistway shall be enclosed in conduit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the elevator machine room is expired and shall be serviced or replaced. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The plastic waste pipe located above the controller shall be guarded or guttered. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational on 110v and battery. | 2/25/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide a code compliant MCP including onsite documents. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Patch all holes in the hoistway. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The upper pit shall be clean. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | Remove the abandoned piping from the hoistway. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Wiring at the top of the hoistway shall be enclosed. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The plastic waste pipe located above the pump unit shall be guarded or guttered. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency phone shall be operational. | 9/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 9/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency lighting shall be operational. | 11/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall work on auxiliary power. | 11/2/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be kept clean. Clean the car top. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Elevator quit running in middle of the inspection. Still need to do relief pressure, standing test, 110v and fire service. | 11/7/2024 |