Inspection
Inspection Details
Equipment ID
3970
3970
Inspection Date
2/26/2019
2/26/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Christopher Bolin
Christopher Bolin
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
18
18
External ID
862f483e-148c-4e82-965e-9bbe54affa85
862f483e-148c-4e82-965e-9bbe54affa85
Location
Bowen Apartments
6140 RAYTOWN RD, RAYTOWN, MO
6140 RAYTOWN RD, RAYTOWN, MO
Owner
Canyon View Property
6140 RAYTOWN RD, RAYTOWN, MO 64133-4096
6140 RAYTOWN RD, RAYTOWN, MO 64133-4096
Billing
Attn: Bowen Tower Senior Apartments
6140 RAYTOWN RD, RAYTOWN, MO 64133-4096
6140 RAYTOWN RD, RAYTOWN, MO 64133-4096
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | did not have test weights to perform the 5 year portion of the test | 5/27/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, provide working phone line to the elevator controller | 6/13/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone does not have a working phone line, provide working phone line to the elevator controller | 12/30/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The machine room fire extinguisher does not have an inspection tag on it | 5/27/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | a copy of the state operating certificate is to be posted in the machine room | 5/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | provide maintenance control program on site documents | 5/27/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the elevator pit | 5/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emergency lights did not work | 10/4/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Need to guard the cab fan from the inside of the cab so that accidental contact with the fan blades cannot happen | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room, fire extinguisher inspection tag expired in 2022 | 8/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace burnt out machine room lightbulbs | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not work | 8/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | provide on site maintenance logs and MCP | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Worm gear shaft seal is leaking so badly that the catch pan overflows, every time the elevator runs a stream of oil comes out of the seal. repair/replace seal 8.6.1.6.2 | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Update machine room fire extinguisher, inspection tag is from 2021, have fire extinguisher inspected and tagged annually | 12/3/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace/repair machine room lights | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Install sign on car operating panel identifying this car as #2 elevator, this is the elevator on the right when in the hall looking at the elevators | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Worm gear shaft seal is leaking, repair/replace seal - written compliance. Not done on 11/7/2025. still not done on 7/1/2026. | 8/20/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | escape hatch shall be locked and openable only from the top of the car without the use of special tools. | 8/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights did not work with the 110 power off | 8/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell did not work with the 110 power off and the emergency phone doesn’t work at all | 8/14/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit light not working | 8/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean the pit | 8/20/2026 |