Inspection
Inspection Details
Equipment ID
5820
5820
Inspection Date
3/28/2019
3/28/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
d2a74f14-a027-4e56-bbf8-258221cd124e
d2a74f14-a027-4e56-bbf8-258221cd124e
Location
Sycamore Hills Elementary
15208 E 39TH ST S, INDEPENDENCE, MO
15208 E 39TH ST S, INDEPENDENCE, MO
Owner
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Billing
Attn: Independence School District
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Independence School District
201 N FOREST AVE, INDEPENDENCE, MO 64050
Phone: (000) 000-0000
Email: Geri_frink@isdschools.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | provide key onsite for the fire service keyswitch, could not test fire service | 3/28/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | maintain dry pit, at the time of the inspection there was standing water in the pit | 2/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | No | No | replace the emergency light battery, it is dead | 3/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair the top of car inspection station, it would not run in the down direction | 2/11/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | repair fire service phase 1 keyswitch, it did not recall the elevator | 8/6/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | replace emergency light battery, it is dead | 2/11/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | the pit shall be kept dry. | 11/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/3/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | standing water in the pit, maintain a dry pit | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | cortop work light bulb is missing, install a new bulb | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | the location of the 110 volt breaker for the elevator cab lights is not marked down in the machine room, could not find breaker for the lights | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag is from 2020, have the fire extinguisher inspected and tagged annually | 10/27/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | could not find the 110 volt breaker for the elevator cab lights, could not test emergency lights and alarm on battery power | 10/27/2025 |