Inspection
Inspection Details
Equipment ID
12984
12984
Inspection Date
3/15/2019
3/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
William Gorden, Jr.
William Gorden, Jr.
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
c7055cd2-e22f-436e-bc80-e5377ccd4f9f
c7055cd2-e22f-436e-bc80-e5377ccd4f9f
Location
Marriott St Louis Grand
900 WASHINGTON AVE, SAINT LOUIS, MO
900 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Marriott St Louis Grand
800 WASHINGTON AVE, SAINT LOUIS, MO 63101-1202
800 WASHINGTON AVE, SAINT LOUIS, MO 63101-1202
Billing
Attn: Marriott St Louis Grand
800 WASHINGTON AVE, SAINT LOUIS, MO 63101-1202
800 WASHINGTON AVE, SAINT LOUIS, MO 63101-1202
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Left handrail should be replaced due to cracks | 9/12/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Need to replace right handrail. | 9/12/2025 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 802.7 | No | No | Replace all worn step rollers. 8.6.8.7 | 9/12/2025 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(c) | No | No | Provide job specific wiring diagrams. | 9/12/2025 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(a) | No | No | Provide maintenance control program documents. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.4 | No | No | Replace both handrails. Splitting noted on outboard and inboard sides. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Replace step demarcation lights. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.4 | No | No | Both handrails need to be replaced due to cracks. | 9/12/2025 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | No | No | Reinspection required, brake torque tests not performed. | 9/12/2025 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Left handrail needs replaced | 9/12/2025 |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.15.18 | No | No | Walk on plate switches shall be made operable. | 9/12/2025 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.3a | No | No | The stop button buzzer at the top landing is not sounding and shall be repaired. | 9/12/2025 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | No | The brake torque could not be tested on the initially due to the need for a specific tool. Reinspection for the brake torque is required. | 10/30/2024 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | No | The brake torque could not be tested on the initially due to the need for a specific tool. Reinspection for the brake torque is required. REINSPECT IN 14 DAYS | 11/25/2024 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | Yes | Brake failed torque test. Red-tagged, Re-inspection required | 11/27/2024 |