Inspection
Inspection Details
Equipment ID
24264
24264
Inspection Date
3/6/2019
3/6/2019
Inspection Type
New Installation
New Installation
Inspector Name
James Mueller
James Mueller
Mechanic Name
Jacob Williams
Jacob Williams
Relief Valve Pressure
Slide
Instantaneous
Instantaneous
Governor Rope Pull
50/200
50/200
Door Closing Force
26
26
External ID
1381e6f8-fa8f-44aa-bf6f-905a99cf2a48
1381e6f8-fa8f-44aa-bf6f-905a99cf2a48
Location
2311 Locust
2311 Locust, St. Louis, MO
Phone: (314) 865-5200
Email: amnechita@kenrickdesign.com
2311 Locust, St. Louis, MO
Phone: (314) 865-5200
Email: amnechita@kenrickdesign.com
Owner
Attn: UNK
Mendenhall Partnership LLC
1485 S. 18th Street, St. Louis, MO 63104
Phone: (314) 653-0800
Email: amnechita@kenrickdesign.com
Mendenhall Partnership LLC
1485 S. 18th Street, St. Louis, MO 63104
Phone: (314) 653-0800
Email: amnechita@kenrickdesign.com
Billing
Attn: UNK
Kone, Inc
9324 Dielman Industrail Drive, Olivette, MO 63132
Phone: (314) 991-1158 Ext: 3146097441
Email: rachel.mazzola@kone.com
Kone, Inc
9324 Dielman Industrail Drive, Olivette, MO 63132
Phone: (314) 991-1158 Ext: 3146097441
Email: rachel.mazzola@kone.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Test the machine room heat detectors. | 3/7/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | No | No | The Phase 1 visual indicator does not work. | 3/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.5 Counterweight Runby Data Plate | No | No | A maximum runby sign is required. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.9 - Power closing of doors or gates | 8.11.2.1.1(i) | No | No | The door time label has not been completed. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle hangers. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle fire gib. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | The governor switch does not function. Elevator Red Tagged. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle hangers. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle fire gib. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post a current state operating certificate in the machine room. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Maintenance/repair records and fire service monthly testing checklist are missing. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Install the center hoistway door hangers at all floors. | 3/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Install the center fire gibs on all hoistway doors. | 3/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | MO State operating certificate not located in the machine room. |