Inspection
Inspection Details
Equipment ID
11582
11582
Inspection Date
3/19/2019
3/19/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
UNK
UNK
External ID
d0ab1480-4273-4563-a627-0c6ef5c92e3f
d0ab1480-4273-4563-a627-0c6ef5c92e3f
Location
US Bank- South County
110 S COUNTY CENTER WAY, SAINT LOUIS, MO
110 S COUNTY CENTER WAY, SAINT LOUIS, MO
Owner
Attn: US Bank- Overland
US Bank- Overland
15839 MANCHESTER RD, ELLISVILLE, MO 63011-2224
US Bank- Overland
15839 MANCHESTER RD, ELLISVILLE, MO 63011-2224
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.2.8 | Yes | Yes | Need to check door closing force. Did NOT red tag. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Need to check door restrictor. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Need to check hoistway door locks. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Need to check pit switch. | 3/18/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Need to test fireman's service. Did NOT red tag. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The humidity in the elevator machine room is significantly higher than the elevator controller is designed for due to recent flooding. The humidity in the machine room shall be reduced to proper levels for the elevator controller and other equipment in the machine room to operate as designed. | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The hydraulic oil in the hydraulic controller for this elevator is milky in color indicating that the oil is contaminated with water. The elevator pump motor on this unit is submersed in oil and will fail with excessive water contamination. The hydraulic oil in this unit shall be changed. | 3/18/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/18/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | No | No | Machine room shall be equipped with a Fire rated access door. | 3/18/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State Certification shall be displayed in machine room. | 3/18/2026 |